Cubicle-Type Gas-Insulated Medium-Voltage Switchgear (C-GIS)

Cubicle-Type Gas-Insulated Medium-Voltage Switchgear (C-GIS) is designed for primary medium-voltage power distribution applications, combining a compact metal-enclosed structure with a sealed SF₆ gas insulation system and vacuum circuit breaker technology.

Available in 12 kV, 24 kV, 36 kV and 40.5 kV rated-voltage classes, with project-specific protection, control and interlocking configurations.

Key Ratings

  • Rated Voltage

    12 / 24 / 36 / 40.5 kV

  • Rated Current

    Up to 3150 A

  • Short-Time Withstand Current

    Up to 40 kA

  • Rated Frequency

    50 / 60 Hz

  • Circuit Breaker Type

    SF₆ Gas Insulation

Available Configurations

  • 01

    Incoming Feeder

    Incoming power supply with circuit breaker, protection and control functions.
  • 02

    Outgoing Feeder

    Feeder protection and switching for downstream distribution circuits.
  • 03

    Bus Coupler

    Bus sectionalizing and coupling between switchgear sections.
  • 04

    PT / Voltage Transformer Panel

    Voltage measurement, protection and monitoring according to project requirements.
  • 05

    Metering Panel

    Voltage and current measurement for system metering and monitoring.

Technical Specifications

Rated Voltage 12 kV 24 kV 36 kV 40.5 kV
Typical System Voltage 10 / 11 kV 20 / 22 kV 33 kV 35 kV
Rated Frequency 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz
Power-Frequency Withstand Voltage 28 kV 50 kV 70 kV 95 kV
Lightning Impulse Withstand Voltage 75 kV 125 kV 170 kV 185 kV
Rated Current Up to 3150 A Up to 3150 A Up to 2500 A Up to 2500 A
Rated Short-Time Withstand Current Up to 40 kA Up to 40 kA Up to 31.5 kA Up to 31.5 kA
Switchgear Type Gas-Insulated Switchgear Gas-Insulated Switchgear Gas-Insulated Switchgear Gas-Insulated Switchgear
Switching Technology Vacuum Circuit Breaker Vacuum Circuit Breaker Vacuum Circuit Breaker Vacuum Circuit Breaker
Insulation Medium SF₆ Gas Insulation SF₆ Gas Insulation SF₆ Gas Insulation SF₆ Gas Insulation
Gas Compartment Hermetically Sealed Hermetically Sealed Hermetically Sealed Hermetically Sealed
Main Busbar Material Copper Copper Copper Copper
Busbar Arrangement Single / Double Busbar Options Single / Double Busbar Options Single / Double Busbar Options Single / Double Busbar Options
Internal Arc Classification Project-Specific Project-Specific Project-Specific Project-Specific
Cable Entry Bottom / Project-Specific Bottom / Project-Specific Bottom / Project-Specific Bottom / Project-Specific
Protection & Control Project-Specific Project-Specific Project-Specific Project-Specific
Installation Indoor Indoor Indoor Indoor
Applicable Standards IEC 62271-200 / IEC 62271-100 IEC 62271-200 / IEC 62271-100 IEC 62271-200 / IEC 62271-100 IEC 62271-200 / IEC 62271-100

Standards, Testing & Documentation

IEC-Oriented Design

IEC-Oriented Design

Designed with reference to applicable IEC requirements and project specifications.

Factory Routine Testing

Factory Routine Testing

Routine tests are carried out before shipment according to product configuration and applicable requirements.

Project Documentation

Project Documentation

Technical datasheets, drawings and test records can be provided for project review.

Download Product Catalogue

Get the detailed product information, technical data and typical configurations.

Download Product Catalogue

Discuss Your Cubicle-Type Gas-Insulated Medium-Voltage Switchgear Requirements

Share your system voltage, rated current, short-circuit rating, single-line diagram and project specifications with our engineering team.

return-top

    Need a quote for your project?

    Share your requirements and our team will typically respond within 1 business day.

    Fields marked with an * are required.

    Full Name *

    Email Address *

    Company Name

    Country / Region *

    WhatsApp / Mobile

    Project Requirements / Message *

    WeChat

    WeChat QR Code

    Scan to Chat

    Open WeChat and scan to connect