Switching Substation

Item Umit Data
Rated voltage kV 12
Rated frequency Hz 50
Rated current of main busbar/maximum rated current of fuse A 630,125
Rated short-time withstand current of main circuit and grounding circuit kA/S 20,3
Rated peak withstand current of main circuit and grounding circuit kA 50
Rated short-circuit closing current of main circuit and grounding circuit kA 50
Full capacity breaking number of load switch times 100
Circuit breaker breaking current kA 31.5
Rated closed-loop breaking current A 630
Rated transfer current A 870
Mechanical lifespan times 2000
1-minute power frequency withstand voltage (peak) relative to ground/isolation fracture kV 42,48
Lightning impulse withstand voltage (peak value) phase to phase, ground/isolation fracture kV 75,85
Secondary circuit 1-minute power frequency withstand voltage kV 2
Protection level IP3X