VS1-11
The 11KV VS1 circuit breaker is an indoor high-voltage vacuum circuit breaker designed for international standard adaptation and special high-voltage applications. It is compatible with three-phase 50Hz/60Hz power frequency AC circuits, with a rated voltage of 11KV. It is primarily used for high-voltage distribution network control and protection in foreign-related large industrial enterprises, multinational industrial parks, international standard distribution network projects, and certain specialized industries (such as oil and gas extraction, large data centers). This product adheres to both domestic GB standards and international IEC/ANSI standards, featuring optimized insulation levels, electrical parameters, and structural compatibility based on the 10KV model.
It employs an integrated modular design for the mechanism and circuit breaker, offering a compact structure and reliable operation. The product supports both fixed and withdrawable trolley installation forms, compatible with international standard high-voltage switchgear. Equipped with high-precision vacuum arc extinguishing chambers and wear-resistant contact materials, it delivers stable arc extinguishing performance and robust breaking capacity. With no harmful gas emissions or noise pollution, it effectively addresses the complex loads, harsh operating conditions, and voltage stability requirements of foreign-related projects and specialized industries. It can swiftly interrupt overload, short-circuit, and zero-sequence fault currents, ensuring the safe and stable operation of distribution networks and equipment in special scenarios. Suitable for working conditions at altitudes ≤3000m and ambient temperatures ranging from -30°C to 50°C, it is the preferred equipment for foreign-related high-voltage distribution networks and specialized industries.
The product manufacturing strictly follows the domestic GB1984, DL/T403 standards, and also complies with international IEC60056, IEC62271-106, and ANSI standards. It has passed international authoritative certifications such as KEMA and CE, and its electrical parameters and installation dimensions are compatible with similar international products. It can directly adapt to foreign-related projects, multinational industrial parks, and imported power distribution equipment without additional modifications, meeting international project acceptance requirements and reducing equipment adaptation costs for foreign-related projects.
The epoxy resin APG process is used to cast the insulation cylinder as a whole, with sufficient anti creepage distance. The rated short-time power frequency withstand voltage (1 minute) can reach 80kV (relative to ground, phase to phase), 90kV (fracture), and the rated lightning impulse withstand voltage (peak) can reach 130kV (relative to ground, phase to phase), 150kV (fracture), and can stably withstand 11KV high voltage loads; The rated short-circuit breaking current can reach 40~50kA, with balanced breaking performance. It can reliably break various loads and fault currents, adapting to the complex load and voltage fluctuation requirements of special industries such as oil and gas extraction and data centers.
Adopting a modular structure design, core components such as electrical components and arc extinguishing chambers can be interchanged with international VS1 circuit breakers of the same voltage level. At the same time, it is compatible with both domestic and international standards of high-voltage switchgear. The handcart model adopts an international standard plug-in structure, which is smooth and reliable in contact, and can achieve live extraction maintenance, reducing power outage range and downtime, and improving the convenience of operation and maintenance of foreign-related projects.
the parts are made of high quality alloy materials that are temperature resistant, corrosion resistant and anti-aging. After special anti-corrosion treatment and optimized sealing structure, they have good dust-proof, moisture-proof, salt fog resistant and electromagnetic interference resistant properties. They can adapt to the corrosive environment in the oil and gas exploration plant area, the constant temperature and humidity environment in the data center, and the complex climate conditions in the transnational park. The mechanical life can reach 30000 times, and the breaking times of full capacity short circuit current can reach 80 times, with high operation stability.
International standard intelligent control interfaces are reserved, and internationally common intelligent monitoring units can be installed to achieve remote opening and closing, real-time monitoring of operating status (current, voltage, temperature, vacuum degree), fault self diagnosis and remote fault location functions. It supports linkage with international mainstream distribution network automation systems, adapts to the intelligent and unmanned operation and maintenance needs of foreign-related projects, and can provide a multilingual operation and maintenance interface to facilitate the operation and maintenance management of international projects.
The rated current of this product covers 1600A~4000A, and different specifications such as 2000A, 3150A, 4000A can be customized according to scene requirements. The rated short-circuit breaking current is 40~50kA, the rated short-circuit closing current can reach 100~125kA, the rated short-circuit duration is 4s, the closing time is 35~75ms, the opening time is 20~50ms, the closing bounce time is ≤ 2ms, the opening and closing asynchrony is ≤ 2ms, and the contact resistance is ≤ 100 μ Ω, meeting the high load requirements of foreign-related projects and special industries.
The suitable environmental conditions are: the daily average relative humidity does not exceed 95%, the monthly average does not exceed 90%, the earthquake intensity does not exceed 8 degrees, there is no severe vibration, strong chemical corrosion (can be customized for anti-corrosion upgrade), explosion hazard, and places with serious pollution; Oil and gas extraction scenarios can be customized with enhanced anti-corrosion and explosion prevention solutions, while data center scenarios can be customized with electromagnetic interference prevention and temperature adaptation solutions.
Each product undergoes strict type testing, factory inspection, and international standard certification, accompanied by complete international and domestic testing reports, certification documents, and multilingual product manuals; Supporting customized manual/electric operation modes, intelligent monitoring functions, and special protection solutions, it can be used with international standard fuse handcarts, isolation handcarts, voltage transformer handcarts, and other supporting products. It has strong universality and accessories can be conveniently supplied globally.
Providing you with the most trusted energy solutions in an unpredictable world.
Contact Us| Item | Unit | Data | ||||
| Rated voltage | kV | 11 | ||||
| Rated frequency | Hz | 50 | ||||
| Rated insulation level | 1-minute power frequency withstand voltage (effective value) | kV | 32 | |||
| Lightning impulse withstand voltage (peak value) | kV | 85 | ||||
| Rated current | A | 630 | 630 | 1250 | 1600 | |
| 1250 | 1250 | 1600 | 2000 | |||
| 2000 | 2500 | |||||
| 2500 | 3150 | |||||
| 4000 | ||||||
| Rated short-circuit breaking current | kA | 20 | 25 | 31.5 | 40 | |
| Rated short-time withstand current | 20 | 25 | 31.5 | 40 | ||
| Rated short-circuit closing current | 50 | 63 | 80 | 100 | ||
| Rated peak withstand current | 50 | 63 | 80 | 100 | ||
| Rated short-circuit duration | S | 4 | ||||
| Rated operating sequence | O – 0.3s – CO – 180s – CO | |||||
| Split 180s Split 180s Split (40kA) | ||||||
| Rated short-circuit current breaking times | 30/20 | |||||
| Mechanical lifespan | 10000 | |||||
| Rated breaking current of a single capacitor bank | 630 | |||||
| Rated back-to-back capacitor bank breaking current | 400 | |||||
| Grounding fault breaking current of different phases | kA | 10 | ||||
| Allowable wear and accumulated thickness of dynamic and static contacts | 3 | |||||
The core difference lies in the compatibility of standards and scene positioning, which are not interchangeable. The 11KV model focuses on foreign-related projects and international standard distribution networks, compatible with both domestic and international standards, suitable for specific voltage scenarios of 11KV, and structurally compatible with similar international products; The 10KV model focuses on domestic high-voltage distribution network backbone lines, only following domestic standards, with slightly higher breaking capacity (up to 63kA), and emphasizes domestic urban and park distribution network scenarios. There are differences in rated voltage, insulation level, and structural dimensions between the two, and forced exchange may result in arc extinguishing failure, equipment failure, and inability to meet international project acceptance requirements.
Sure. This product can be customized with anti-corrosion and explosion prevention strengthening solutions. The components have undergone special anti-corrosion treatment and can withstand harsh environments such as corrosive gases and dust in oil and gas extraction plants. At the same time, the vacuum arc extinguishing design has no fire or explosion hazards and meets the safety requirements of the oil and gas extraction industry. The rated voltage is 11KV and the breaking current is 40-50kA, which is suitable for the high-voltage distribution network load of oil and gas extraction plants. It can be responsible for the power supply control and fault protection of extraction equipment and supporting equipment of transmission pipelines, ensuring the safety and stability of oil and gas extraction.
Sure. This product has passed international authoritative certifications such as KEMA and CE, and can provide internationally recognized type test reports, certification documents, and factory inspection reports, fully meeting the acceptance requirements of foreign-related projects and export projects; At the same time, it can provide product manuals, operation manuals, and technical parameter manuals in multiple languages such as Chinese, English, and German, which are suitable for the operation and maintenance management needs of international projects. Specific language versions can be customized according to project requirements.
Sure. This product adopts international standard structural design, and the dimensions and interfaces of core components such as arc extinguishing chamber, operating mechanism, and electrical components are compatible with international VS1 circuit breakers of the same voltage level. It can be directly interchanged without additional customization, greatly improving the operation and maintenance convenience of foreign-related projects, reducing accessory procurement costs, and providing global convenient supply of accessories to avoid downtime caused by shortage of accessories in foreign-related projects.
Sure. This product reserves an international standard intelligent control interface, and after installing an intelligent monitoring unit, it can seamlessly integrate with mainstream international distribution network automation systems (such as Schneider and Siemens distribution network automation systems) to achieve remote opening and closing, fault alarm, status monitoring, and remote fault location functions. The data transmission protocol complies with international standards and can be linked with the intelligent dispatch platform of international projects to achieve intelligent and unmanned operation and maintenance, adapting to the intelligent management needs of foreign-related projects.