KYN28-6
6kV indoor metal armored movable switchgear is a mainstream equipment in industrial and municipal distribution networks, which complies with GB/T 3906-2020 and DL/T 404-2018 standards and is suitable for medium voltage distribution scenarios such as power plants, chemical parks, and urban distribution networks. The equipment adopts a modular armored structure, which separates different functional components into independent compartments (circuit breaker room, busbar room, cable room, instrument room). It has the characteristics of strong breaking capacity, high safety performance, and flexible expansion, and can achieve centralized distribution, control, and rapid fault removal of electrical energy, adapting to the power supply needs of medium and large loads.
Equipped with medium voltage vacuum circuit breakers, the short-circuit breaking capacity can reach 31.5kA-50kA, which can effectively cut off short-circuit fault currents. It has strong short-term withstand current ability and is suitable for complex working conditions such as large motor starting in industrial scenarios.
Equipped with multiple mechanical and electrical interlocks such as circuit breaker and isolation switch interlocks, handcart position and grounding switch interlocks, cabinet door and internal component interlocks, etc., to prevent dangerous operations such as false closing and load pulling from the source, ensuring the safety of operation and maintenance personnel.
The cabinet adopts standardized modular units, which can flexibly combine different functional cabinets such as circuit breaker cabinets, metering cabinets, PT cabinets, and contact cabinets according to power distribution needs. During later expansion, there is no need for overall renovation, only adding new modules and connecting them to the busbar.
The cabinet is made of corrosion-resistant cold-rolled steel plate processed by CNC machining, and the surface is treated with electrostatic spraying, which can withstand harsh indoor environments such as high temperature, humidity, dust, etc; The internal components are made of anti-aging materials and can operate stably in environments ranging from -25 ℃ to 40 ℃.
Reserved installation interfaces for intelligent instruments and sensors, which can integrate functions such as power quality monitoring, fault location, temperature monitoring, etc., support docking with distribution network automation systems, and achieve remote monitoring and intelligent regulation of distribution circuits.
The rated current range of the product is 630A-2500A, and the rated short-time withstand current is 20kA-50kA (3s); Supports two configurations of SF6 circuit breaker or vacuum circuit breaker, which can be selected according to the user’s cost budget and usage needs; The default protection level of the cabinet is IP4X, which can be upgraded to IP54 to meet the requirements of high dust and high humidity scenarios; Provide comprehensive factory inspection reports and type test certificates to ensure product compliance.
Providing you with the most trusted energy solutions in an unpredictable world.
Contact Us| PROJECT | UNIT | DATA | |
| Rated voltage | kV | 6 | |
| Rated frequency | Hz | 50 | |
| The rated current of the main bus | A | 630/1250 | |
| Current rating | A | 630/1250 | |
| Ground Loop Rated Short-Time Withstand Current (2S) | kA | 31.5 | |
| Rated short-time withstand current of main circuit (4S) | kA | 25/31.5 | |
| Rated peak withstand current (peak) | kA | 63/80 | |
| Rated short-circuit interrupting current | kA | 25/31.5 | |
| Rated insulation level | 1 minute power frequency withstand voltage | kV | intermittent to the ground: 20 |
| Fracture: 23 | |||
| Withstand voltage for lightning impulses | kV | intermittent to the ground: 40 | |
| Fracture: 46 | |||
| Ingress protection | The shell is IP4X | ||
The core difference lies in the adaptation of load and performance parameters: 6kV products have higher breaking capacity and rated current, and can adapt to medium and large industrial loads (such as large motors and production lines); 3.3kV products focus more on compactness and are suitable for small end loads, with different application scenarios and distribution levels.
Common causes include: loose busbar joints leading to corona discharge, circuit breaker mechanism jamming, transformer failure, etc. It is recommended to immediately stop running and have professional operation and maintenance personnel troubleshoot. Disassembling on your own is prohibited to avoid safety accidents.
Sure. By integrating intelligent monitoring modules and remote control functions, the device can upload real-time operating parameters (current, voltage, temperature), automatically alarm and trigger protection actions in case of faults, fully adapting to the needs of unmanned distribution rooms.
The venue must meet the following requirements: indoor dry and ventilated, ambient temperature of -25 ℃ to 40 ℃, relative humidity ≤ 95% (no condensation); Ground bearing capacity ≥ 8kN/㎡, with sufficient maintenance space reserved (≥ 800mm on both sides of the cabinet and ≥ 1500mm on the front); Stay away from flammable, explosive, and corrosive gas environments.
The warranty period for cabinet body is 5 years, and the warranty period for core components such as vacuum circuit breakers and transformers is 3 years. If non-human faults occur during the warranty period, the components can be replaced free of charge and on-site maintenance services can be provided. After the warranty period, lifelong technical support and parts supply will be provided.