KYN28-7.2
7.2kV indoor metal armored movable switchgear is a core equipment in medium voltage distribution systems that is suitable for high voltage conditions and large capacity loads. It complies with GB/T 3906-2020 and DL/T 404-2018 standards and is mainly used in high voltage distribution scenarios such as power plants, large substations, and new energy projects. The equipment adopts a high-strength armored compartment structure, optimizes insulation performance and breaking capacity, and has the characteristics of high rated parameters, strong safety and stability, and high intelligence. It can achieve the distribution, control, and precise fault removal of high-voltage electrical energy, and is suitable for high-voltage, large capacity, and long-distance distribution needs.
Optimized for 7.2kV high voltage working conditions, the rated current can reach 1250A-4000A, the short-circuit breaking capacity can reach 50kA-80kA, and the short-term withstand current ability is strong. It can be adapted to high voltage and large capacity distribution scenarios such as power plant auxiliary electricity and large transformer outlets.
By using composite insulation materials and vacuum insulation technology, the insulation distance between phases and relative to ground is greatly increased. Equipped with insulation monitoring devices, the insulation status can be monitored in real time. At the same time, the cabinet adopts a grounding shielding design to effectively prevent high-voltage leakage and corona discharge, ensuring the safety of equipment and personnel.
It can seamlessly integrate with new energy generation systems such as wind power and photovoltaics, support a wide voltage input range, have reactive power compensation and power quality adjustment functions, effectively cope with the volatility of new energy generation, and ensure the stable operation of the distribution system.
Optimize the design of the circuit breaker mechanism, use silent operating components, with a noise level of ≤ 60dB during operation. At the same time, the cabinet is equipped with shock absorbers to reduce vibration and noise pollution during equipment operation, and is suitable for power plant control rooms and precision laboratory power distribution scenarios.
Integrated equipment health monitoring system can collect real-time data such as current, voltage, temperature, insulation status, etc., predict equipment failures through big data analysis, provide operation and maintenance suggestions, and support full lifecycle traceability of components to reduce operation and maintenance costs.
The product supports SF6 vacuum hybrid circuit breaker or full vacuum circuit breaker configuration, which can be selected according to user needs; The default protection level is IP4X, which can be upgraded to IP54. Explosion proof type (Ex d IIB T4) can be customized for special scenarios; The intelligent module supports integration with new energy control systems and power grid dispatch systems to achieve collaborative regulation; Provide comprehensive type test reports, factory inspection reports, and third-party certification certificates to ensure product compliance and reliability.
Providing you with the most trusted energy solutions in an unpredictable world.
Contact Us| PROJECT | UNIT | DATA | |
| Rated voltage | kV | 7.2 | |
| Rated frequency | Hz | 50 | |
| The rated current of the main bus | A | 630/1250 | |
| Current rating | A | 630/1250 | |
| Ground Loop Rated Short-Time Withstand Current (2S) | kA | 31.5 | |
| Rated short-time withstand current of main circuit (4S) | kA | 25/31.5 | |
| Rated peak withstand current (peak) | kA | 63/80 | |
| Rated short-circuit interrupting current | kA | 25/31.5 | |
| Rated insulation level | 1 minute power frequency withstand voltage | kV | intermittent to the ground: 20 |
| Fracture: 23 | |||
| Withstand voltage for lightning impulses | kV | intermittent to the ground: 40 | |
| Fracture: 46 | |||
| Ingress protection | The shell is IP4X | ||
The 7.2kV product focuses on domestic high-voltage medium to large capacity scenarios (such as power plants and new energy projects), and is compatible with the national standard high-voltage distribution hierarchy; The 6.6kV product focuses on overseas special voltage scenarios and complex working conditions such as mines and ships, and there are significant differences in the distribution systems and application areas that the two are suitable for.
The equipment is equipped with a wide range voltage adaptation module and reactive power compensation device, which can automatically adjust the output voltage and power factor. At the same time, it is linked with the new energy control system to respond in real time to fluctuations in wind and photovoltaic power generation, avoiding voltage instability from impacting the distribution system.
The cabinet adopts a ventilation and heat dissipation structure, equipped with a heat dissipation fan and temperature sensor. When the temperature exceeds the set value, the fan will automatically start to dissipate heat; The core components are made of high-temperature resistant materials, and the cabinet layout is optimized to reduce heat accumulation in densely populated areas, ensuring stable operation of the equipment in high-temperature environments.
Sure. The device supports mainstream communication protocols such as MODBUS and IEC 61850, and can be directly connected to existing intelligent distribution systems and power grid dispatch systems to achieve data sharing, remote control, and collaborative protection, without the need for large-scale modifications to existing systems.
Required. Due to the high voltage level of 7.2kV, the equipment structure and wiring are complex, requiring a professional team with high voltage distribution installation qualifications to carry out installation and commissioning, in order to avoid equipment failure or safety accidents caused by improper operation. The manufacturer can provide on-site technical support.