XGN20
The 20kV air-insulated ring main unit is a core hub equipment for high-voltage distribution networks. It is compatible with high-voltage distribution networks in some domestic cities, large energy bases, and 20kV distribution systems in some European countries. Using dry air as the insulating medium, it integrates core technologies such as high-voltage insulation enhancement, intelligent dispatch linkage, and high-capacity current flow. It possesses functions such as main line power supply, ring network interconnection, and new energy grid connection. The equipment combines high-voltage performance with compact design, enabling centralized control of high-voltage distribution networks within limited spaces. It is the preferred equipment for upgrading high-voltage distribution networks and large energy projects.
Utilizing multiple layers of insulating barriers and reinforced insulating materials, the insulation strength is increased by 20% compared to standard requirements, effectively resisting high-voltage arcs and voltage surges, and preventing insulation breakdown failures.
It supports seamless docking with power grid dispatching systems and new energy control platforms, and possesses functions such as load forecasting, power quality analysis, and remote precise regulation and control, enabling unmanned operation and maintenance of high-voltage distribution networks.
Optimized design through vertical layering and horizontal zoning, resulting in a cabinet volume 60% smaller than traditional equipment of the same voltage level. It can be installed in urban underground distribution rooms and compact distribution rooms in energy bases.
The core components have a service life of over 25 years and a long maintenance-free period. Compared to SF6 high-voltage equipment, it eliminates the costs of gas procurement and recycling, reducing the full lifecycle cost by over 30%.
Executive standards: GB/T 3906-2020, IEC 62271-201, EN 50027; Rated current: 2000A-4000A; Short-circuit breaking current: 31.5kA-40kA; Protection level: IP4X (outdoor type IP55); Installation methods: indoor floor-mounted, embedded in underground distribution room, outdoor prefabricated; Optional configurations: power quality monitoring module, intelligent energy storage operating mechanism, grid dispatching linkage terminal.
Providing you with the most trusted energy solutions in an unpredictable world.
Contact Us| No. | Name | Unit | Value |
| 1 | Rated Voltage | kV | 20 |
| 2 | Rated Frequency | Hz | 50 |
| 3 | Rated Current of Main Busbar / Maximum Rated Current of Fuse | A | 630, 125 |
| 4 | Rated Short-time Withstand Current of Main Circuit & Grounding Circuit | kA/S | 20, 3 |
| 5 | Rated Peak Withstand Current of Main Circuit & Grounding Circuit | kA | 50 |
| 6 | Rated Short-circuit Making Current of Main Circuit & Grounding Circuit | kA | 50 |
| 7 | Full Capacity Opening Times of Load Switch | times | 100 |
| 8 | Fuse Breaking Current | kA | 31.5 |
| 9 | Rated Closed-loop Breaking Current | A | 630 |
| 10 | Rated Transfer Current | A | 1600 |
| 11 | Mechanical Life | times | 2000 |
| 12 | 1min Power Frequency Withstand Voltage (Peak) – Phase-to-Phase & Phase-to-Earth / Isolation Break | kV | 50/60 |
| 13 | Lightning Impulse Withstand Voltage (Peak) – Phase-to-Phase & Phase-to-Earth / Isolation Break | kV | 125/145 |
| 14 | 1min Power Frequency Withstand Voltage of Secondary Circuit | kV | 2 |
| 15 | Protection Class | IP3X |
There is no significant difference. The reinforced insulation structure and optimized layout ensure that the insulation performance meets standards, and the air insulation poses no leakage risk. It is easier to operate and maintain, making it more advantageous in urban distribution networks and energy projects.
It is adaptable, possesses load regulation and anti-fluctuation capabilities, and can respond to photovoltaic energy in real time.